ATEX fan for refrigerator recycling – Zone 22 inside, 5,400 m³/h at 3,300 Pa
Dust, lint and Zone 22? We can do that.
In a refrigerator recycling plant, the exhaust air downstream of the cyclone is anything but clean: residual dust and lint remain in the medium, and the air still has to be moved on safely for the customer's process. For exactly this task we built an explosion-proof centrifugal fan.
The special feature is the zone classification: inside the fan, ATEX Zone 22 applied, outside it did not. An explosive dust atmosphere is therefore expected only rarely and briefly during operation – but it has to be handled by design, while the surroundings require no such version.
As so often in plants of this kind, the choice fell on our horizontal WLN design, mounted on the suction flange, which was adapted to the customer's requirements. This design connects directly to cyclones, ducts and filters – an advantage that pays off again and again in tight plant layouts.
Inside the fully welded housing with a cleaning opening runs a backward-curved high-performance impeller. It is driven by a 2-pole 11 kW motor in V1 mounting position via a frequency converter. The fan reaches a volume flow of 5,400 m³/h at a total pressure difference of 3,300 Pa.
Safe operation in a dust-laden atmosphere is ensured by the equipment:
- vibration switch for monitoring imbalance and vibration
- speed sensor to monitor the operating condition
- earthing screws to discharge static electricity
- cleaning opening in the housing for maintenance and inspection
- pressure-side transition piece for connection to the plant
With dust and lint, discharging static electricity is not a minor detail but part of the protection concept. Together with vibration and speed monitoring, the result is a unit that reports its condition before it becomes a fault.
The fact that the customer once again chose a product from ZENNER Ventilatoren Werke GmbH goes back to their experience with our fans. That is the kind of feedback that tells us the most: those who come back had a good experience with the first unit.
Another example of the fact that a fan is not just a fan.
ZENNER Ventilatoren – Durable. Low-maintenance. Quality since 1947.
Made in Germany.
This version is suitable when:
- dust-laden exhaust air has to be moved downstream of a cyclone, filter or separator
- ATEX Zone 22 applies inside the fan but no zone applies outside
- the fan is to be mounted directly onto a suction or plant flange
- the plant layout calls for a horizontal, compact design
- operating conditions are to be monitored (vibration, speed)
- the flow rate is controlled by a frequency converter
It is not suitable when:
- an explosive atmosphere is also present outside the fan – a version for the external zone is then required
- high medium temperatures occur, as covered by a hot-gas fan
- highly abrasive media are conveyed that require a wear-protected version
- free-standing installation without a plant flange is intended
- Application: refrigerator recycling / exhaust air downstream of the cyclone
- Fan type: centrifugal fan, horizontal WLN design, mounted on the suction flange
- Medium: exhaust air laden with residual dust and lint
- Explosion protection: ATEX Zone 22 inside, no zone outside
- Volume flow: 5,400 m³/h
- Total pressure difference: 3,300 Pa
- Drive: 11 kW, 2-pole, V1 mounting position, controlled by frequency converter
- Impeller: backward-curved high-performance impeller
- Housing: fully welded, with cleaning opening
- Safety: vibration switch, speed sensor, earthing screws
- Accessories: pressure-side transition piece, customer-adapted suction flange
- Manufacturing: made to order in Germany